General


The measurements of the wall are incorrect, ‘neighbouring’ construction thicknesses and sizes of the wall has conflicting points that are too close to one another.
The areas of the subareas have been reduced in size to fit the construction
Window … in room ... cannot be separated in window frame and glass plane. The construction is now 100% glass.
The heating battery is too large, power of the heating battery is adjusted.
The room has heating in the floor, walls, or ceiling but has no thermal active layer within the structure
HVAC in construction heating, given power …, calculated maximum power … W/m2; calculation uses the maximum power.
Amount of orientations of NIOR is more than allowed, particularly NIOR=10. MAXOR=8. Subroutine worent.for.
You cannot retrieve the writing lock with the reading lock.

We have collected all reports in the attached file. This is a file that is still being developed, so this version is a draft version.

KnownErrorsList_2024 en

Heat loss


Calculation ‘heat loss’ completed successfully.
The ’Heat Loss’ calculation failed.
The room is calculated according to ISSO 57.
It is not possible to apply a qv10 to the rooms according to ISSO 57 industry. An infiltration rate needs to be added in the template ventilation. A ventilation rate of 0,2 is applied.
The ventilation in this room does not suffice the Building decree. Extra supply of air from outside is needed for the calculation.
Calculation temperature unheated room is not correct (heat balance). The room probably borders exclusively unheated rooms.
In room ’...' a source of the ventilation air through the ventialtion system needs to be determined, if there is chosen for an air flow according to the Building Decree.
The qᵥ10 value for infiltration is too low or too high in combination with the ventilation system
HVAC ‘...’ in room ‘...’ is not applicable. This unit is ignored. Also see emission template ‘...’ used for room ‘...’.

Cooling load


Calculation ‘cooling load’ completed successfully.
The determination of the palpable power is possibly not according to table 1 NEN 5067, the calculation automatically assumed with 60% palpable power.
Calculation ‘cooling load’ has failed

Building simulation


Calculation ‘building simulation’ completed successfully.
Calculation ‘building simulation’ failed.
Program quit – subroute pschrom.f. Dry Bulb temperature in K negative.
The control room for air cooling is not supplied correctly. The first room has now become the control room.
Manage with ATG – not consistent input. IREGLC is not consistent with IATG.
HVAC’...’ of room ‘…' is ignored in calculation, because maximum devices is already reached.
Building simulation has a mapping error and closed. Mechanical supply without air flow.
Climate data for climate ... for building simulation are not available.
This Room has no content.
In this complex room the calculations of the coefficient of haze for the comfort cube happens in a simple manner.
The Building simulation stopped because of a mapping error; Room has one or more sources in construction.

Back to Results