Within a project multiple air handling systems or air handling units may be defined. Within the HVAC template you may select the air handling system to link to the room. An air handling system can be defined based on multiple elements; for examples of climate systems refer to ISSO 43.

Ventilation system type

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

The ventilation system type is displayed depending on the input in the input screen for the Air handling resource; this type cannot be changed directly.

Ventilation control

  • EPG

The ventilation control is displayed based on the type of ventilation system, and the regulation and control. The ventilation control is applied in the calculation of energy performance in the EPG module.

Supply

Mechanical supply

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

This box indicates whether a mechanical supply for the air handling system is present. Checking this box affects the ventilation system type in the top of the Air handling screen.

Number of fans

  • EPG

This number represents the number of ventilators within the air handling unit. This input can only be specified in case the Ventilation power is determined using the detailed method in the EPG calculation. The ventilation power in the system also includes the ventilation power on room level, as is the case with fan coils.

Publications

NEN 8088-1, paragraaf 7.3.2.3

Actually installed nominal power

 

Nominal power

  • EPG

This is the nominal power per fan in W. In case multiple fans have been defined, the nominal power is multiplied by the number of fans. The ventilation power in the system also includes the ventilation power at room level, as is the case with fan coils.

Warming-up

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

This indicates whether the heating of air caused by the supply fan should be taken into account. The amount of heating should be specified in Kelvin.

  • Default: the heating by the supply fan is taken as 1.5 K
  • User defined: the heating by the supply fan can be specified between 0 and 4 K

Supply grilles

  • EPG

The regulation (control) of the supply grilles can be specified in case no mechanical supply is available, and consequently the supply air is extracted from outside. The supply grilles partially determine the ventilation control type in the top of the screen, which is used for the energy performance EPG calculation.

  • No control
  • Wind pressure driven flow Δp ≤ 1 Pa
  • Wind pressure driven flow 1 Pa <Δp ≤ 5 Pa
  • Wind pressure driven flow 5 Pa <Δp ≤ 10 Pa
  • Time control without zoning
  • CO2 control on indirect supply in each living room, without zoning
Publications

NEN 8088-1, paragraaf 5.5.2.2.1

System-related ventilation for heating and cooling – Tabel 2

Ventilation exhaust

Mechanical exhaust

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

This box indicates whether a mechanical exhaust for the air handling system is present. Checking this box affects the ventilation system type in the top of the Air handling screen.

Decentralized exhaust (System C; variant)

  • Gebouwsimulatie
  • Warmteverlies

Checking this box indicates that a variant on ventilation system C should be used in the heat loss calculations for housing. In this variant the air is extracted for each room separately (demand-controlled ventilation), rather than being extracted centrally in the kitchen, bath room, and toilet. As a result the heat loss calculations are performed with a façade which is more airtight; a lower qv,10 value can be specified.

Publications

ISSO Publicatie 51 (2017), paragraaf 4.7.2

Natural supply of ventilation air, mechanical exhaust per room

ISSO Publicatie 51 (2012), paragraaf 4.3.2.3

System C: Natural supply and mechanical exhaust

ISSO Publicatie 51 (2012), paragraaf 4.3.1.1

Residences/residential buildings that comply with the new construction requirements of the Building Decree –Tabel 4.2

Number of fans

  • EPG

This number represents the number of ventilators within the air handling unit. This input can only be specified in case the Ventilation power is determined detailed for the energy performance in the EPG, as should be indicated in the Project settings.

Publications

NEN 8088-1, paragraaf 7.3.2.3

Actually installed nominal power

Nominal power

  • EPG

This is the nominal power per fan in W. In case multiple fans have been defined, the nominal power is multiplied by the number of fans.

Warming-up

  • Gebouwsimulatie
  • EPG

This indicates whether the heating of air caused by the exhaust fan should be taken into account. The amount of heating should be specified in Kelvin.

  • Default the heating by the exhaust fan is taken as 1.5 K
  • User defined the heating by the exhaust fan can be specified between 0 and 4 K

Ventilator specifications

Electric source

  • EPG

For the electric source it should be indicated whether the ventilators for housing are driven by an alternating current or direct current engine. This input has no effect in the case of non-residential buildings.

  • Alternating current motor
  • Direct current motor
Publications

NEN 8088-1, Bijlage D

Determination of nominal electrical fan power for calculation

 

Control

  • Gebouwsimulatie
  • EPG

This control specifies whether it is possible to control back the air flow volume. Back control is possible only if the fan power is specified. No back control is surcharged when the minimum fan requirements are determined using the flat rate method.

  • No control (CAV)
  • Throttling control (VAV). This will affect the total pipe resistance, the operating point of the device, and consequently the yield.
  • Intake vane damper control (VAV)
  • Blade adjustment control (VAV)
  • High / low control (VAV). This regulates the fan from two positions, high or low.
  • Fan speed control (VAV). This controls the number of revolutions per unit time of the fan.
Publications

NEN 8088-1, paragraaf 7.3.3.2.2 tabel 17

Actually installed power for the entire building

 

Redcution control per room possible

  • Gebouwsimulatie
  • EPG

Check the box indicating that there is regulation. This is only possible when VAV (Variable Air Volume) is selected. When you check “Regulation possible per room up to,” and you enter, for example, 20%, then up to 20% of the specified design airflow will be regulated down.

Regulation is only possible if the actual installed ventilation capacity is specified.

For the minimum ventilation requirements determined by the standard method, no regulation is considered.

Publications

NEN 8088-1, paragraaf 7.3.3.2.2 tabel 17

Actually installed power for the entire building

 

VLA methodology

Equivalence ventilation

  • Warmteverlies
  • EPG

According to the VLA methodology, it is possible to apply equivalence for energy-saving ventilation solutions in residential construction. Equivalence for ventilation systems results in an adjusted correction factor for the control system \( f_{\text{reg}} \) and an adjusted air volume flow factor \( f_{\text{sys}} \). For the heat loss calculation, \( q_{\text{vbuild}} \) is important.

Description

  • Warmteverlies
  • EPG

Statement regarding an equivalency declaration, which will also be included in the reports.

Air flow power factor (fsys)

  • EPG

Specification of the air volume flow factor \( f_{\text{sys}} \) according to the equivalency report, which replaces the standard air volume flow factor according to Table 2 of NEN 8088-1:2012.

Control system correction factor (freg)

  • EPG

Specification of the control system correction factor \( f_{\text{reg}} \) according to the equivalency report, which replaces the standard correction factor according to Table 2 of NEN 8088-1:2012.

Reduction factor flow rate (qvbuild)

  • Warmteverlies

Specification of the reduction factor on \( q_{\text{vbuild}} \) for a demand-controlled ventilation system according to the equivalency report, which replaces the standard value from ISSO. This has an impact on determining the connected load for heat loss. The standard reduction factors for various systems are given in the image below.

Publications

ISSO Publicatie 51 & ISSO Publicatie 53 (2017), paragraaf 5.1.1

Heat loss due to outside air infiltration

NEN 8088-1, paragraaf 5.5.2.2.1

Actually installed capacity for entire buildings

 

Heating/cooling coil

The coil specifications below should be entered according to the product data from the supplier. The screen above is the display for a cooling coil, but it is the same for the heating coil except for the relative humidity (RH).

Heating / cooling coil present

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

This indicates whether a heating/cooling coil is present.

Thermal power

  • Gebouwsimulatie
  • Unlimited; with this option it is assumed that the heating/cooling coil has unlimited power. Therefore, no maximum temperatures for the water supply and exhaust are applicable in this case;
  • Limited value: the total thermal power should be specified here. This power should, at least, be consistent with flow rate as specified for the supply fan. Thus, the power of the coil as it is put in the air handling unit is concerned here.
In a building simulation the right amount of ventilation (for the rooms to be calculated) is used in the calculations by means of a fraction. This fraction for the cooling coil is determined from the fraction of the ventilation. The thermal power is determined at the water supply temperature, water exhaust temperature, air temperature, and relative humidity at the entrance and the exit which have been specified. If the thermal power is used only to realize the supply temperature, sufficient power should be available, i.e. 2 kW per 100 m³ air. In this case the default values ​​for water supply- and exhaust temperature and air conditions can be applied without changing them. (Note that specifying a total power of 99,999 kW leads to a very large flow which can cause small inaccuracies.)

Power specifications

  • Gebouwsimulatie

The type of temperature specifications can be indicated here if the thermal power has a limited value:

  • Vabi default: The default temperatures are applied, see table below;
  • User defined: The temperatures can be specified manually.
Water supply Water drainage Air inlet Air output
Warm 90 °C 70 °C -7 °C 20 °C
Cool 6 °C 12 °C 27.4 °C and 80% RH 20 °C and 98% RH

Water inlet

  • Gebouwsimulatie

This is the water supply temperature at which the thermal power is computed, and it indicates the temperature of the supply water used for cooling or heating. The water supply temperature used by the software for calculations is determined by Temperatures of the linked Distribution resource.

Water outlet

  • Gebouwsimulatie

This is the water exhaust temperature at which the thermal power is computed, and it indicates the temperature of the exhaust water which remains after cooling or heating. This temperature is used to compute the flow rate through the coil.

Air inlet

  • Gebouwsimulatie

This is the air supply temperature at which the maximum thermal power is determined. The air supply temperature is the outside temperature in general, but in case of heat recovery / recirculation it is computed by the building simulation.

and RH

  • Gebouwsimulatie

This is the relative humidity of the supply air. The moisture conditions at the inlet are important as these conditions are mainly responsible for determining the power, and consequently the efficiency of the cooling coil when performing dehumidification.

Air outlet

  • Gebouwsimulatie

This is the air exhaust temperature at which the maximum thermal power is determined. Together with the inlet temperature this is used to determine the air flow over the coil. The building simulation performs its calculations using an air heating curve.

And RH

  • Gebouwsimulatie

The moisture conditions at the inlet are important as mainly these conditions determine the power, and consequently the efficiency of the cooling coil in case of dehumidification.

Note: The above temperatures are the (maximum) power specifications of the cooling and/or heating coil. The actual temperatures (or heating curves) used in the calculations, are determined in the associated distribution network.

Distribution net

  • Gebouwsimulatie

The distribution network for this air handling unit is selected here from the networks which have been defined within the current project library. This distribution network is linked to a generation resource and a generator which can deliver heat or cold to the coil

Heat recovery

Heating the ventilation air from outside requires energy. A lot of this energy may be saved by adjusting the amount of supply air for ventilation to the need for ventilation. When applying heat recovery, the heat from the exhaust air is used to preheat the supply air. Heat recovery is only possible when both mechanical supply and mechanical exhaust are selected.

Heat recovery present

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

In this box it can be specified whether heat recovery is present.

Decentralized heat recovery

  • Warmteverlies
  • EPG

In this box it can be specified whether decentralized heat recovery is present. Decentralized heat recovery includes ClimaRad systems.

Heat recovery in combination with natural supply (system E)

  • Warmteverlies
  • EPG

If a decentralized heat recovery has been specified, in this box it can be indicated whether system E is applied. System E can be used only in housing construction, i.e. the computation of a non-residential building with system E is not possible.

Efficiency

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

The thermal, flat rate efficiency should be indicated here. A choice should be made from the predefined types according to NEN 7120.

Publications

ISSO Publicatie 51 & ISSO Publicatie 53 (2017), Bijlage C en ISSO Publicatie 57 (2017), bijlage D

Heat recovery efficiency.

NEN 8088-1, paragraaf 6.3.2.2

Preheating supply air via HRV (Heat Recovery Ventilation) system

Type of system Thermal efficiency Description
Custom value The thermal (flat rate) efficiency may be specified manually. This value should be discussed for equivalence, and it should be rounded to a multiple of 0.05.
Tube heat exchanger 65% A tube heat exchanger (cross-flow heat exchanger or twin-coil heat exchanger) consists of flat and corrugated sheets of aluminium or stainless steel which have been manufactured alternately flat and corrugated. Supply- and exhaust air flows along these plates. The supply- and exhaust flows are strictly separated; therefore no moisture recovery from the supply air occurs.
Twin-coil heat exchanger 60% Twin Coil
Cold storage with heat pump;

 

40%
Heat pipe 60%
Rotating heat exchanger 70% A rotating heat exchanger is a slowly rotating, intermittent heat exchanger made from small aluminium tubes. It is based on a heat-accumulating element in the shape of a wheel which is alternately run through supply and exhaust air. The thickness of the heat exchanger determines the heat capacity.

The heat exchanger is rotating at a speed ranging from 1 to about 10 revolutions per minute. The temperature of the supply air can be kept reasonably constant by varying the angular velocity of the heat exchanger. The hot exhaust air is run through the aluminium tubes which take on the temperature of the exhaust air. The rotating wheel then runs the tubes through the supply air. This supply air is heated by the hot aluminium tubes. This same heat exchanger can be applied in offices with a cooling system to precool the hot supply air from outside using the relatively cool inside air during summer.

 

Counter flow heat exchanger 75% A counter flow heat exchanger, or tilt valve system, consists of fans, a tilt valve, and two cassette cases with aluminium cassettes for heat storage. Air from the building is blown outside through a cassette box by means of a valve housing. The aluminium cassettes in the cassette case ensure that the heat from the suctioned air is stored in the cassettes. After a while the valve in the valve housing tilts, after which the cold outside air is led inside through the heated cassettes. The stored heat in these cassettes warms up the outside air. Efficiencies of 90% are possible with this system and also moisture recovery is a possibility. A combination is possible with adiabatic cooling, in which the temperature drops due to atomization.

Besides heat recovery from hot ventilation air during winter, cold recovery in a cooled building is possible in the same way from the relative cold inside air during summer.

Kantherm heat exchanger 90% The Kantherm heat exchanger recovers heat, cold, and moisture from the exhaust air depending on the season. During winter the Kantherm recovers both heat and moisture, and in summer it can ventilate freely (free cooling) or recover cold.

 

Moisture recovery present

  • Warmteverlies

Choice option when rotating heat exchanger or Enthalpy Heat Exchanger are present.

Frost protection

  • Warmteverlies

Choice option in heat loss when heat recovery type is not an Enthalpy Heat Exchanger.

The options are:

None / unknown (100% outside air) – ISSO 2017 calculates without Heat recovery; ISSO 2023 calculates with 75% efficiency.

Fan-speed reduction / temporary unbalance (100% outside air) -ISSO 2017 calculates without Heat recovery; ISSO 2023 calculates with 75% efficiency.

Preheating outside air – Heat Recovery is included

This option is applicable for the Heat Loss Standards of 2017: an input field for the temperature after heat recovery will appear. If the option is applied for ISSO 51 2023, then a field for the temperature after preheating before heat recovery will appear.

Publications

ISSO Publicatie 51 & ISSO Publicatie 53 (2017), 

Frost protection

 

Air temperature after recovery

  • Warmteverlies

The air temperature after heat recovery is indicated here. This value is used in the heat loss calculations. If only heat recovery is present in the system, this temperature is blown into all rooms, unless heating by the ventilator is specified, which is not included in the efficiency of the heat recovery. In the latter case the heating of the ventilators is added to the temperature after heat recovery.

Publications

ISSO Publicatie 51 & ISSO Publicatie 53 (2017), ISSO publicatie 57

Specific heat loss due to ventilation

 

Temperature after preheating for heat recovery

  • Warmteverlies

The temperature entered here is the temperature of the air before the heat recovery system if “Preheating outside air” is selected for Frost Protection in ISSO 51 2023. This temperature is used as the input to the heat recovery system, and then the supply air temperature is determined based on the efficiency of the heat recovery system.

Divergent correction factor

  • EPG

By default, a correction factor of 0.8 (practical efficiency correction) is applied on top of the heat recovery efficiency. This correction accounts for air- or heat leakages. In case you diverge from the standard correction factor of 0.8, this should be supported by measurements or calculations according to NEN 8088, Appendix C.

Publications

NEN 8088-1, paragraaf 6.3.2.2

Determination of the practical efficiency correction factor of an HRV (Heat Recovery Ventilation) system

 

Insulated supply channel

  • EPG

Specification of insulation for the duct section located within the building envelope.

Publications

NEN 8088-1, paragraaf 6.3.2.2

Bepaling van de praktijkrendementcorrectiefactor van een WTW-installatie

 

Constant volume control HRV (Heat Recovery Ventilation)

  • Warmteverlies

Specification of whether the HRV system has a constant volume control to compensate for pressure changes by adjusting the supply and exhaust fans; the control must be active at all ventilation switch settings.

Publications

NEN 8088-1, paragraaf 6.3.2.2

Bepaling van de praktijkrendementcorrectiefactor van een WTW-installatie

 

The dissipation of ventilation is embedded in the COP

  • Gebouwsimulatie
  • Warmteverlies
  • EPG

If the dissipation of ventilation (heating of the ventilation air by the ventilator) is included in the efficiency of the heat recovery, the specified heating of the ventilator (if available) is not surcharged any more.

Publications

NEN 8088-1, paragraaf 17.4.3

Central air handling – Calculation values

 

Bypass EPG

  • EPG

This option allows you to specify whether the heat recovery uses a (partial) bypass. If this is the case the cool outside air can cool the building during the summer months without being post heated by the heat recovery. This will have a beneficial effect on the EPC.

Publications

NEN 8088-1, paragraaf 5.6.2

Purge ventilation in residential construction

 

Bypass GS

  • Gebouwsimulatie

Here you can indicate whether the heat recovery uses a bypass. A bypass allows cool outside air to cool the building during summer months without being reheated by the heat recovery, which has a favorable effect. The options are:

1. Without bypass
2. Supply air temperature controlled bypass – the bypass is used to achieve the desired supply air temperature as efficiently as possible.
3. Outdoor temperature controlled bypass – the bypass is used based on specified outdoor temperatures.

Newsletter item: Bypass in building simulation

Evaporation cooling (Adiabatic cooling)

Evaporation cooling present

  • Gebouwsimulatie

With the adiabatic cooling option, it is possible to perform calculations that incorporate the use of adiabatic cooling. Adiabatic cooling can be achieved in various ways.

Type

  • Gebouwsimulatie

Here you can specify the type of evaporative cooling present when evaporative cooling is selected. Currently, the following options are available:

  • Outside Air Heat Exchange efficiency: Indirect Evaporative Cooling, this type is based on cooling the outside air through humidification. Using a heat exchanger, the supply air for the air handling unit is pre-cooled with the chilled saturated outside air.
  • Oxycom Dew Point: This is an efficient, compact, and lightweight heat exchanger that combines (dew point) cooling with high-efficiency heat recovery. The technology used here is the OXYCELL technology. This technology provides cooling in a completely natural way and does not use refrigerants.

Efficiency

  • Gebouwsimulatie

When the type Outside Air Heat Exchange is selected, you can specify the efficiency of the system here.

Air mixer

Air mixer box present

  • Gebouwsimulatie
  • EPG

In this box it can be specified whether air mixing, or recirculation, is applied in the system. The recirculation is only taken into account in the energy performance calculation EPG if these calculations are performed based on the actual installed ventilation power. This means that the recirculation is not taken into account for air flows according to the minimum ventilation requirements.

Minimum outside air

  • Gebouwsimulatie
  • EPG

If air mixing is applied, the percentage of supply air which consists of fresh outside air (not recycled air) can be specified in this field. The remaining supply air will be extracted from exhaust air. The fraction of fresh outside air should comply with the minimum ventilation requirements for the energy performance calculation EPG.

If outside air temperature <

  • Gebouwsimulatie

The maximum outside temperature below which the outside air is allowed to be mixed with recirculation air is specified here.

Humidification / dehumidification

Humidifier/dehumidifier present

  • Gebouwsimulatie
  • EPG

This box allows you to indicate whether a humidifier/dehumidifier is present and should be taken into account in the calculations. The specifications of the dehumidifier can be indicated in this screen. The effectiveness of the coil is determined based on the thermal power delivered at a given water supply temperature, air supply temperature, and moisture conditions. The software is able to determine the maximum thermal power under various conditions (air volumes, supply temperatures, moisture content, etc). The true air volumes (in the given conditions) are specified from the supply fan, and the supply temperatures from the heating curves for water and air. The cooler/ dehumidifier is controlled based on temperature and moisture content.

Setpoint

  • Gebouwsimulatie

The setpoint determines when the system must humidify/dehumidify the air. This part is activated when the relative humidity is below the setpoint for humidification and above the setpoint for dehumidification. The moisture conditions are important as these determine the effectiveness of the cooling coil for a large part in case of dehumidification.

Publications

ISSO Publicatie 32 (2011), paragraaf 5.3

Design Criteria for humidity

 

Type

  • EPG

The type of humidifier is only applicable for EPG calculations (Source: SenterNovem). If the selected type is the electricity-driven steam vaporizer, then the energy source will be electricity in the EPG calculation. For the other types, the required energy is provided by the heating system and whatever generator is specified for.

  • Gas-driven steam vaporizer: Steam is blown into the air through a tube with holes. The steam is generated in one or more small gas boilers by the evaporation of water. These devices heat up water using a heating element driven by gas. The obtained vapour is added to the air in a controlled way.
  • Electricity-driven steam vaporizer: Steam is blown into the air through a tube with holes. The steam is generated in one or more small electric boilers by the evaporation of water. These devices heat up water using a heating element driven by electricity. The obtained vapour is added to the air in a controlled way.
  • Ultrasonic humidifier: In this method, water is atomized by means of ultrasonic vibrations in aerosols. The air in the channel in which these vibrations take place absorbs these aerosols quickly. The movement of air is achieved using a ventilator. The relative humidity can be kept at a high level with this method.
  • Adiabatic humidifier: The humidifier works through the expansion and contraction of air; literally adiabatic means: without heat exchange with the environment. So no heat exchange occurs in an adiabatic process, but rather compression leads to heating and expansion to cooling.

Moisture recovery present

  • EPG

In this box it can be indicated if moisture recovery is present. If this is the case, a reduction to the energy need for humidification is surcharged.

Publications

NEN 7120, paragraaf 18.2

Determination of energy use for humidification – calculation rules

 

Air control

Mechanical ventilation control

  • EPG

The mechanical ventilation control can be specified here. The Ventilation control type in the top of the screen is determined based on the mechanical ventilation control. This Ventilation control type is applied in the energy performance calculation EPG.

  • No control
  • Time control without zoning
  • Time control with two or more zones,
  • CO2 control exhaust only
  • CO2 control in residential area
  • CO2-control with two or more zones,
  • CO2 control in residential area with cooker
Publications

NEN 8088-1, paragraaf 5.5.2.2.1

System-related ventilation for heating and cooling needs – Tabel 2

NEN 8088-1, paragraaf 5.6.2

Purge ventilation in the residential building category

 

Ventilation in night mode when warming up the building

  • Warmteverlies

In buildings with mechanical supply of ventilation air, the calculations can take it into account when the ventilation is in night mode when warming up the building. During this night mode the ventilation performs at 50% power in housing and it is inactive in non-residential buildings. The power required for (possibly) warming up the ventilation air has been charged already. This power is not used during heating of the building (partly for housing), therefore, it can be used to heat up the building. As a result, the required power for heating of the ventilation (partly for housing) air is subtracted from the power to be installed in the room. In heat loss calculations, it is always safer not to work with the ventilation in night mode when warming up the building.

Publications

ISSO Publicatie 51 (2017), paragraaf 4.8.4

Allocable surcharge for operational limitation

ISSO Publicatie 53 (2012), paragraaf 4.8.3

Allocable surcharge for operational limitation

 

Conditional night heating present

  • Gebouwsimulatie

The central air handling unit is controlled for conditional nighttime heating based on conditions in the Control Room. If the room temperature in the space to be calculated falls below the activation temperature, nighttime heating will activate. The system will then switch to the airflow rate for conditional nighttime heating. Conditional nighttime heating with ventilation air is only possible if:

  • An airflow rate for conditional nighttime ventilation is specified under Ventilation.
  • The airflow rate for conditional nighttime ventilation is greater than the airflow rate for (normal) nighttime ventilation.
  • A nighttime mode is set in the emission template.

If conditional night heating present is selected, the nighttime heating curve will be followed. These heating curves, as well as the nighttime mode for both Distribution and Air Handling, must be specified.

ON when air temperature of the room <

This is the room temperature at which the air heater and fans turn on. When the Control Room temperature is colder than this temperature, nighttime heating will activate. This is also known as the activation temperature. This setting only becomes visible if conditional nighttime heating is selected.

OFF when air temperature of the room >

\[°C\] Standard 17 °C GS
This is the room temperature at which the air heater and fans turn off. When the room is warmer than this temperature, nighttime heating will not activate. This is also known as the deactivation temperature. This setting only becomes visible if conditional nighttime heating is selected.

Conditional night cooling

  • Gebouwsimulatie

In this screen you can specify whether the night cooling is provided by the intake of additional air and/or by the central air cooler. The central air handling system is controlled based on the conditions in one of the rooms for conditional night cooling. The night cooling is activated when the room temperature of this room is below the switching temperature and the temperature difference (between inside and outside) is larger than specified. In this case the flow rate for conditional night cooling is applied. Conditional night cooling with ventilation air is only possible if:

  • A flow rate for night mode has been specified in the Ventilation template;
  • The flow rate at conditional night ventilation is greater than the flow rate at (normal) night ventilation.
ON when air temperature of the room >|url=lbk.regeling.vwnachtkaan1.htm

[° C] Standard 23 °C BS
This is the room temperature at which the air cooler and ventilators are activated. Night cooling will be activated when the room temperature is above this specified temperature. This is also called the activation temperature. This setting only becomes visible if conditional night cooling has been chosen.

And outside air temperature >|url=lbk.regeling.vwnachtkaan2.htm

[° C] Standard 5 °C BS
This is the outside temperature at which the air cooler and ventilators are activated. Night cooling will be activated when the outside temperature is above this specified temperature. This setting only becomes visible if conditional night cooling has been chosen.

And difference between inside and outside air temperature >|url=lbk.regeling.vwnachtkaan3.htm

[K] Standard 5 K BS
Conditional night cooling may only be activated if the difference between the room temperature and the outside temperature is greater than a specified minimum value. The room temperature is considered at the end of the previous hour. This setting only becomes visible if conditional night cooling has been chosen.

OFF when air temperature of the room <|url=lbk.regeling.vwnachtkuit.htm

[° C] Standard 18 °C BS
This is the room temperature at which the air cooler and ventilators are deactivated. Night cooling will not be activated when the room temperature is below this specified temperature. This is also called the deactivation temperature. This setting only becomes visible if conditional night heating has been chosen.

Air Distribution

Ducts present

  • EPG

This box indicates ducts are present for the ventilation system. In case of a central system with air ducts a correction is applied to the chargeable ventilation capacity depending on the airtightness class of the ducts.

Ducts indoor or inside building

  • EPG

In this box it can be indicated whether the ducts are indoor or inside the building. This is used in the energy performance calculation EPG for housing; in case of non-residential building this option does not affect the results. This box only appears when ducts are present as well as a heating coil in the system. The distribution efficiency for the heating system is determined partially based on this checkbox.

Publications

NEN 7120, paragraaf 14.3.3.1

Calculation values for internal distribution efficiency

 

Insulated ducts

  • EPG

In this box it can be indicated that the ducts have been insulated, which affects the energy performance EPG calculation both for housing and non-residential buildings. This box only appears when ducts are present as well as a heating coil in the system. The distribution efficiency for the heating system is determined partially based on this checkbox.

Publicaties

NEN 7120, paragraaf 14.3.3.1

Calculation values for internal distribution efficiency

Airtightness class

  • EPG

The air tightness class of the ducts in the system can be specified here. This is only required if ducts are present. Depending on the specified class, a correction is applied to the ventilation capacity to be accounted for, as shown in Table 4 of NEN 8088.

The allowable air leakage of components is related to air tightness classes (A, B, C, and D) according to the NEN-EN 1751 standard. Class D is the most airtight. To achieve the desired air volume, a fan will need to blow more than 20% more air into a duct that meets air tightness class A than into a duct that meets air tightness class C.

Publications

NEN 8800, paragraaf 5.5.3

Correction for air leakage in ventilation ducts, tabel 4

 

Location air supply

  • EPG

In case of housing, it is indicated whether a central supply or a supply at the facades is applied. This distinction is used in the energy performance calculation. The location of air supply is only asked for if air ducts are present and a heating coil has been specified. The distribution efficiency of the heating system is determined partly based on the location of air supply.

Publications

NEN 7120, paragraaf 14.3.3.1

Calculation values for internal distribution efficiency

 

Temperatures

  • Gebouwsimulatie
  • Warmteverlies

The heat curves are important in the air handling unit to optimize the energy reduction. In temperatures, the heating curve is determined, which can be done in one of the following three ways:

  • Default; In this setting a constant temperature of 18 °C is applied in both daytime and night time operation;
  • Constant: In this setting a constant, user specified, temperature is applied in both daytime and night time operation;
  • Curve: The complete heating curve is defined manually. For all values of outside temperature (Toutside) a value of the heating- or cooling water (Twater) can be specified. Separate curves can be defined for daytime operation and night time operation.
Publications

ISSO Publicatie 68 (2002)

Energetically optimal heating and cooling curves for air-conditioning systems in office buildings

 